2.0 Installation, Con guration and System Interface, continued
2.2 ACM-96 and ACM-96G
2.2.1 A2304 Generator Controller Con guration
1. The A2034 logic board is located in the electronics compartment of the APU
enclosure. Locate the 4-position Dip Switch and set switch 2 in the OFF position.
For the new con guration, switches 1 and 3 should be on, and switches 2 and 4
should be off.
2. Remove the Y alarms harness and connect the 15 pin male mini mate-n-lock
connector directly to J2 of the 704-619 board.
3. Install provided alarm jumper to J4 of the A2034 logic board.
Fig. 2-2, A2304 Dip Switch Con guration
Fig. 2-3, Y Alarms Harness
Fig. 2-4, Alarms Jumper