Argus Technologies Ltd. 018-587-C0 Rev A WC
Printed in Canada. © 2008 Argus Technologies Ltd. ARGUS and CORDEX are trademarks of Argus Technologies Ltd. All Rights Reserved. Page 10 of 19
Terminal Description Signal Type Range
Analog Inputs and System Signals
3 and 4; V2 Battery (Charge) Voltage Pos (+) / Neg (-)
0—100Vdc
13 and 14; I1 Load (Discharge) Current Pos (+) / Neg (-) ±50mV
64, 65, and 66; DCCT DCCT Power Supply Pos (+) / Gnd / Neg (-) ±15Vdc / 100mA maximum
67 and 68; B PWR Secondary Power Pos (+) / Neg (-) 20—60Vdc
69 and 70; A PWR Power Pos (+) / Neg (-) 20—60Vdc
Digital Inputs – See Table A for definitions of logic and system
21 and 22; D1 Distribution Fuse/Circuit Breaker Pos (+) or Neg (-) 0—60Vdc
23 and 24; D2 Battery Fuse/Circuit Breaker Pos (+) or Neg (-) 0—60Vdc
25 and 26; D3 LVD Manual In Pos (+) or Neg (-) 0—60Vdc
27 and 28; D4 LVD Manual Out Pos (+) or Neg (-) 0—60Vdc
29 and 30; D5 Converter Fail Pos (+) or Neg (-) 0—60Vdc
31 and 32; D6 Converter I/P Breaker Trip Pos (+) or Neg (-) 0—60Vdc
33 and 34; D7 Unassigned Pos (+) or Neg (-) 0—60Vdc
35 and 36; D8 Unassigned Pos (+) or Neg (-) 0—60Vdc
Alarm Outputs – Can be configured to de-energize on alarm (DOA) or energize on alarm (EOA).
37, 38, and 39; K1 LVD1 NC/COM/NO 60Vdc / 1A
40, 41, and 42; K2 LVD2 NC/COM/NO 60Vdc / 1A
43, 44, and 45; K3 LVD3 NC/COM/NO 60Vdc / 1A
46, 47, and 48; K4 System Minor NC/COM/NO 60Vdc / 1A
49, 50, and 51; K5 System Major NC/COM/NO 60Vdc / 1A
52, 53, and 54; K6 AC Mains Hi/Low NC/COM/NO 60Vdc / 1A
55, 56, and 57; K7 Unassigned NC/COM/NO 60Vdc / 1A
58, 59, and 60; K8 Unassigned NC/COM/NO 60Vdc / 1A
61, 62, and 63; K0 System Fail Output* NC/COM/NO 60Vdc / 1A
– for List 120, add the following:
1 and 2; V1 Load (Discharge) Voltage Pos (+) / Neg (-)
0—100Vdc
5 and 6; GP1 Temp Probe 1 Pos (+) / Neg (-)
0—20Vdc
, with power source
7 and 8; GP2 Temp Probe 2 Pos (+) / Neg (-)
0—20Vdc
, with power source
11 and 12; GP4 Bipolar Voltage Pos (+) / Neg (-)
±60V
– for List 124, add the following:
1 and 2; V1 Voltage 1 Pos (+) / Neg (-)
0—100Vdc
5 and 6; GP1 Voltage 3 Pos (+) / Neg (-)
0—60Vdc
7 and 8; GP2 Voltage 4 Pos (+) / Neg (-)
0—60Vdc
9 and 10; GP3 Voltage 5 Pos (+) / Neg (-)
0—60Vdc
11 and 12; GP4 Temp Probe 1 Pos (+) / Neg (-)
0—20Vdc
, with power source
– for List 125, add the following:
1 and 2; V1 Load (Discharge) Voltage Pos (+) / Neg (-)
0—100Vdc
5 and 6; GP1 Temp Probe 1 Pos (+) / Neg (-)
0—20Vdc
, with power source
7 and 8; GP2 Temp Probe 2 Pos (+) / Neg (-)
0—20Vdc
, with power source
9 and 10; GP3 Bipolar Voltage Pos (+) / Neg (-)
±60V
11 and 12; GP4 Bipolar Voltage Pos (+) / Neg (-)
±60V
15 and 16; I2 Battery (Charge) Current Pos (+) / Neg (-) ±50mV
17 and 18; I3 Current Input 3 Pos (+) / Neg (-) ±50mV
19 and 20; I4 Current Input 4 Pos (+) / Neg (-) ±50mV
– for List 129, add the following:
1 and 2; V1 Load (Discharge) Voltage Pos (+) / Neg (-)
0—100Vdc
5 and 6; GP1 Temp Probe 1 Pos (+) / Neg (-)
0—20Vdc
, with power source
7 and 8; GP2 Temp Probe 2 Pos (+) / Neg (-)
0—20Vdc
, with power source
9 and 10; GP3 Temp Probe 3 Pos (+) / Neg (-)
0—20Vdc
, with power source
11 and 12; GP4 Temp Probe 4 Pos (+) / Neg (-)
0—20Vdc
, with power source
15 and 16; I2 Current Input 2 Pos (+) / Neg (-) ±50mV
17 and 18; I3 Current Input 3 Pos (+) / Neg (-) ±50mV
19 and 20; I4 Current Input 4 Pos (+) / Neg (-) ±50mV
Table B–Wiring connections for CXCP/CXCR
* System Fail output relay is fail-safe and will de-energize during an alarm condition.