2.2 Pole-mount Installations
The APC- PM and APL-PM are designed to be mounted on wooden, steel, or
concrete poles. When used with wooden poles, mounting bolts that go completely
through the pole should be used. When used with concrete poles, an approved
mounting strap should be used. Most codes require the base of the enclosure to be
located at a minimum height from the ground. Always verify height restrictions
before proceeding.
NOTE: THE MAJORITY OF POLES ARE THE PROPERTY OF THE LOCAL
UTILITY. BEFORE INSTALLING AN ENCLOSURE, THE LOCATION AND THE
METHOD OF MOUNTING MUST BE APPROVED BY THE UTILITY.
NOTE: BEFORE INSTALLING THE MTA, ENSURE THAT ALL OPTIONS HAVE
BEEN INSTALLED AND PROPERLY CONNECTED.
2.2.1 Wooden Poles
Materials Required:
Two (2) 5/8” diameter machine bolts (UNC thread) SAE Grade 5 or better, length to
suit pole;
Four (4) 5/8” diameter zinc-plated flat washers;
Two (2) 5/8” diameter hex nuts (UNC thread).
Tools Required:
Auger or drill for boring 3/4” diameter holes through the wooden pole.
Associated sockets or wrenches.
Procedure:
1. Un-box the APC or APL and set the unit on its back (mounting bracket
down).
2. Loosen the enclosure’s front panel hold-down screw and tilt the cover
forward. Remove the cover by sliding (at the hinges) to the right.
3. Loosen the captive screw at the bottom of the units baseplate. Lift the
Modular transformer assembly up and off of the enclosure’s baseplate.
Set the MTA aside.
4. Mark the position for the upper mounting bolt on the utility pole. Drill a
3/4” hole completely through the pole.
5. Use the baseplate as a template. Align the upper hole in the baseplate
with the upper hole in the utility pole (from step 4). The spacing
between the marks should be 4.5” c-c. Drill the lower mounting hole.
6. Place a flat washer on each bolt and insert the mounting bolts through the
baseplate assembly and pole.
7. Secure both bolts using a 5/8” washer and nut. Tighten the nuts until the
flanges on the baseplate’s mounting bracket dig into the wood
approximately 1/4”.
8. Install the Modular Transformer Assembly (MTA) onto the baseplate, (see
section 2.9 MODULAR TRANSFORMER ASSEMBLY).