2.8 External Service Disconnect
2. INSTALLATION
21
The external service disconnect should be placed between the utility power
connection and the APC non-standby power supply. For pole-mount enclosures, it
should be attached directly to the utility pole using 1/4” x 2-1/4” steel wood screws.
If a utility power meter is to be used, its mounting base should be secured in the
same manner. Use a suitable conduit to interconnect the meter base, service
disconnect and power supply enclosure.
IMPORTANT NOTE: A high-magnetic 15 Amp circuit breaker should be used
in order to accommodate the high inrush currents normally associated with
start-up of ferroresonant transformers (400 Amp, no-trip, first half cycle).
Conventional service entrance breakers are not recommended.
High-magnetic breakers for Square D service entrances enclosures are available
from Alpha Technologies.
Device Alpha Part No. Square D
Circuit Breaker 470-013-10 Q0115HM
Alpha BBX Option 020-085-10 Q02-4L70RB
APC
The load side of the circuit breaker is connected to the BLACK wire from the APC’s
receptacle box for 120 VAC/60 Hz operation, (or BROWN wire for 230 VAC/50 Hz
operation); the neutral bus is connected to the WHITE wire from the APC’s
receptacle box for 120 VAC/60 Hz operation (or BLUE wire for 230 VAC/50 Hz
operation). The utility ground connects to the enclosures’s ground terminal. Refer
to photos 2.7.1.1 and 2.7.1.2 on the previous page.
APL
The load side of the circuit breaker is connected to the BLACK wire in the APL’s
terminal block for 120 VAC/60 Hz operation, (or BROWN wire for 230 VAC/50 Hz
operation); the neutral bus is connected to the WHITE wire in the APL’s terminal
block for 120 VAC/60 Hz operation (or BLUE wire for 230 VAC/50 Hz operation).
The utility ground connects to the GREEN/YELLOW tracer wire in the APL’s
terminal block. Refer to photo 2.7.1.b on page 19.
NOTE: Refer to Illustrations 2.8.a and 2.8.b (next page) for wiring detail and service
entrance placement.