Photo 2.11.5.3.d
2. INSTALLATION
33
2.11.5.3 LA-E (230VAC Models) Photo 2.11.5.3.a, .b, .c, .d
Procedure:
The LA-E mounts on the back of the front panel and is secured by means of the
existing screw. This option must be hard-wired into the rack-mount unit by means of
quick-connect connectors.
1. Remove the wing-nut from the screw on the LA-E mounting bracket.
Position the LA-E as shown in Photo 2.10.5.d and secure using the same
screw.
2. Trim the wires supplied with the LA-E so the ends are flush with no copper
wire exposed. Carefully insert the flush end into the quick-splice connector
so the end is flush with the internal wire-stop. Fold this end of the connector
shut and crimp tight using pliers. Repeat this procedure for the other wire.
See Photo 2.11.5.3.a
3. Locate the BLUE wire from the AC power cord. Place this wire into the open
end of the quick-splice connector (connected to the BLUE wire on the
LA-E), fold, and crimp tight. Photos 2.11.5.3.a and .b.
4. Locate the BROWN wire from the AC power cord. Place this wire into the
open end of the quick-splice connector (connected to the BROWN wire on
the LA-E), fold, and crimp tight. Photos 2.11.5.3.a and .b.
2.11 Options,
continued
Brown Wire
(from AC Power Cord)
Blue Wire
(from AC Power Cord)
Quick-connect
Splice connectors
Blue or Brown Wire
(from AC Power Cord)
Blue or Brown Wire
(from LA-E)
Photo 2.11.5.3.cPhoto 2.11.5.3.a Photo 2.11.5.3.b