1.2 Operating Principle
The Modular Transformer Assembly (MTA) contains a ferroresonant transformer,
resonant circuit capacitor, and control panel with line input circuit breaker and output
fuse assembly.
Alpha APC (APL) Series non-standby power supplies utilize ferroresonant
transformer technology to provide line conditioning and voltage regulation. The
primary and secondary windings of the transformer are physically isolated from each
other by a large steel core which significantly reduces the capacitive coupling of
spikes and noise to the secondary winding. This provides a regulated, current-
limited output with excellent isolation and noise attenuation: 120dB common mode;
60dB transverse mode.
An oil-filled resonant AC capacitor is connected to the resonant (secondary) winding
of the transformer forming a
tank circuit
. This provides the resonant circuit function
which contributes to the voltage regulation of the supply. The advantage of this type
of transformer / capacitor design is the ability of the ferroresonant transformer to
regulate its output voltage over a wide range of input voltages and output loading.
Typical output voltages may vary + 3 to 5%, with input voltages variations of + 15%
of nominal line voltage, and output loading of 20 to 100%. This tight regulation is
advantageous in cable television applications as the active devices are protected
from dangerous voltages fluctuations.
Another unique feature of the ferroresonant transformer is its ability to provide
current limiting in the event of a short-circuit. This effect is called foldback. The
transformer’s output current can typically reach 150% of the nameplate output
current rating for a short period of time without damage to the transformer. When
the transformer reaches the saturation point, the output current will decrease
(foldback on itself) to a minimum value, and thereby provide current limiting.
Designs based on ferroresonant transformer are extremely rugged and reliable
offering many years of trouble-free operation.
Alpha’s non-standby power supplies are extremely efficient, having a typical
efficiency rating of 90% or better.
The output waveform from the ferroresonant transformer is not a true sine or square
wave, but is instead a quasi-square wave. NOTE: A true RMS voltmeter must be
used to correctly measure the output voltages.
Ferroresonant ‘Tank’ circuit and resulting output waveform
Ferroresonant
transformer and AC
capacitor
C1
T1
Noisy input waveform
Clean output waveform