2.7 Connecting Utility Power,
continued
2. INSTALLATION
20
Grounding wire (Green/
yellow tracer)
MTA Power Receptacle
Neutral wire (Blue
230VAC/50 Hz)
HOT wire
(Brown 230VAC/50 Hz)
LA-E
Photo 2.7.1.2
APC 230 VAC/50 Hz Wiring
Grounding wire (Green)
LA-M Receptacle
Grounding lug (Internal) 120 VAC Utility Input
MTA Power Receptacle
Photo 2.7.1.1
120VAC/60Hz Wiring
Neutral wire
(White 120VAC/60 Hz)
HOT wire
(Black 120VAC/60 Hz)
5. Connect the utility GREEN with YELLOW tracer GROUND wire to the
grounding-wire-clamp on the baseplate and tighten the
clamping screw. An external grounding clamp is also provided on the
outside of the enclosure for connection to a ground-rod.
6. Reposition the rear tab on the receptacle box into the slot in the baseplate.
Tighten the two (2) captive screws.
7. Reinstall the MTA and tighten the screw.
2.7.1.2 Procedure: (230 VAC, 50 HZ) Photo 2.7.1.2
If the modular transformer assembly is installed it must be completely removed
during utility wiring. To remove the transformer assembly, loosen the captive screw
on the bottom of the baseplate and remove the transformer assembly.
1. Loosen the two captive screws securing the receptacle box. Turn the
receptacle box over to expose the internal wiring.
2. Route the utility conduit through the 0.875” diameter opening at the bottom
of the APC PM Enclosure. Secure the fitting with a lock nut.
3. Connect the utility BROWN-HOT wire (230 VAC; 50 Hz) to the BROWN wire
inside the receptacle box using the existing wire nut.
4. Connect the BLUE-NEUTRAL wire to the BLUE wire inside the receptacle
box using the existing wire nut.
5. Connect the utility GREEN/YELLOW tracer -GROUND wire to the grounding
wire clamp on the baseplate. Tighten the clamping screw. An external
grounding clamp is also provided on the outside of the enclosure for
connection to a ground-rod.
6. Reposition the rear tab on the receptacle box into the slot in the baseplate.
Tighten the two (2) captive screws.
7. Reinstall the MTA and tighten the screw.